High Voltage Disconnect Switch 15.5kV 600A Recloser Bypass: single-phase hookstick switch for outdoor MV lines—insulation, anti-pollution flashover, isolate ground voltage.
High Voltage Disconnect Switch 15.5kV 600A Recloser Bypass: single-phase hookstick switch for outdoor MV lines—insulation, anti-pollution flashover, isolate ground voltage.
General
| Base Type | Distribution Base, Smooth Slots |
| Blade Type | Solid Copper (two blade truss-member) |
| Cantilever Bending Strength – Routine | 1,200 Lbs (5.34 kN) |
| Color – Insulator | Dark Gray |
| Contact | Silver |
| Description – Captive Hardware | Consist of 4 each: 1/2″ 13 Stainless Steel Splined Bolt, 1/2″ Lockwasher and Bronze Nut |
| Insulator Type | Polymer (2 1/4″ Bolt Circle) |
| Material – Base | Galvanized Steel per ASTM A153 |
| Tension Range | 5000 lb |
| Torsional Strength | 3,000 in Lbs (339 N-M) |
| UPC | 096359475927 |
Dimension
| Bolt Length | 8.00 in |
| Weight | 39.808 Ib |
Electrical Ratings
| Arc Distance – Dry | 7.1″ (180.3mm) |
| BIL | 110 kV |
| Creep and Leakage Distance | 17.2″ (436.9mm) |
| Current Overload – 8hr Emergency | 1080 A |
| Current Rating | 600 A |
| Dead-Ending Rating – Working Load | 8,000 Lbs |
| Reference Voltage Limit – Minimum | 14.4kV |
| Temperature Rise – Max. at 600A | 29°C |
| Voltage – Maximum | 15.5 kV |
| Withstand Current – Short Time (10 cycles) | 40kA, asymmetrical |
| Withstand Current – Short Time (2 sec) | 25kA, symmetrical |
| Withstand Current – Short Time (3 sec) | 16kA, symmetrical |
Further information or a personal consultation? Our products and know-how are there to provide solutions.